Estimate backup runtime from UPS energy capacity and load.
Estimate idealized runtime using a UPS energy capacity, connected equipment load and an efficiency allowance.
Runtime hours = capacity Wh × efficiency ÷ 100 ÷ load watts. Minutes equal hours × 60.
A 1,000 Wh UPS at 85% efficiency supporting a 500 W load produces an ideal estimate of 1.7 hours.
UPS discharge curves are nonlinear and quoted VA ratings are not the same as usable Wh. Follow the manufacturer runtime chart for equipment planning.